Fig. B16 – Breathing transformer protected by buchholz
[a] Functioning principle
[b] Transformer with conservator
Fig. B18 – DGPT (Detection of Gas, Pressure and Temperature) protection relay for integral filled transformers
[a] Transformer protection relay (DGPT)
[b] Contacts of the DGPT (cover removed)
Fig. B23 – Examples of self powered relays (Schneider Electric)
[a] VIP 40 for basic transformer protection
[b] VIP 400 series self powered IDMT (Inverse Definite Minimum Time) overcurrent and earth-fault relay
Fig. B28 – Example of functional unit architecture with compartments, favoring service continuity
Fig. B30 – Example of MV/LV interlocking system (per-row:2)
Initial configuration: LV Switchboard energized. MV Load break switch closed. LV circuit breaker closed. Earthing switch open and locked in open position. Key O trapped. Key S trapped.
Step 1: Load break switch closed. LV circuit breaker open and locked. Earthing switch open, locked in open position. Key O free, Key S trapped.
Step 2: Load break switch open, LV circuit breaker open and locked in open position. Earthing switch unlocked, Key O trapped, Key S trapped.
Step 3: Load break switch open, LV circuit breaker open and locked in open position. Earthing switch closed and locked, Key O trapped, Key S free.
Step 4: Load break switch open, LV circuit breaker open and locked in open position. Earthing switch closed and locked, door of transformer cubicle open, Key O trapped, Key S trapped.
Fig. B44 – Ventilation opening locations (per-row:1)
Fig. B52 – Two examples of outdoor substations
[a] Ground level walk-in type
[b] Half buried non walk-in type
Fig. C2 – Associated circuit diagrams
[a] Three-phase star; Four-wire: Earthed neutral
[b] Three-phase star: Three-wire
[c] Three-phase star; Three-wire:Earthed neutral
[d] Three-phase star; Four-wire:Non-earthed neutral
[e] Two-phase star;Three-wire: Earthed neutral
[f] Three-phase delta: Three-wire
[g] Three-phase delta; Four-wire: Earthed mid point of one phase
[h] Three-phase open delta; Four-wire: Earthed mid point of one phase
[i] Three-phase open delta: Earthed junction of phases
[j] Single-phase; Three-wire: Earthed mid point
[k] Single-phase; Two-wire: Earthed end of phase
[l] Single-phase; Two-wire Unearthed
[m] Single-wire: Earthed return (swer)
[n] DC: Three-wire: Unearthed
Fig. E26 – Measurement of the resistance to the mass of earth of electrode (X) using an earth-electrode-testing ohmmeter
[a] the principle of measurement is based on assumed homogeneous soil conditions. Where the zones of influence of electrodes C and X overlap, the location of test electrode P is difficult to determine for satisfactory results.
[b] showing the effect on the potential gradient when (X) and (C) are widely spaced. The location of test electrode P is not critical and can be easily determined.
Fig. E27 – Examples of main LV switchboard and motor control centre
[a] Main LV switchboard - MLVS - (Prisma P) with incoming circuits in the form of busways
[b] MLVS + motor control centre - MCC - (Okken)
Fig. E29 – Final distribution switchboards
Fig. E53 – Examples of applications where the level of harmonics (THD) is either negligible or high, depending on the proportion of loads generating harmonics versus classical loads
Workshops supply:
* Mix polluting charges (computer hardware, inverters, fluorescent lighting) and clean charges (motors, pumps, heaters, etc.).
* Low probability of harmonic's presence THD < 33 %
Offices supply:
* A lot of polluting charges (computer hardware, inverters, fluorescent lighting, etc.).
* High probability of harmonic's presence THD ≥ 33 %
Fig. E64 – Coherent system approach for all components of the electrical installation
Fig. F10 – Circuit supplying socket-outlets
Fig. F47 – The 2 technologies of RCDs
[a] Voltage Independent (VI) technology Electronic circuit not connected to the network
[b] Voltage Dependent (VD) technology Electronic circuit connected to the network
Fig. F48 – Industrial-type CB with RCD module
[a] Industrial type circuit breaker with integrated RCD function
[b] Acti 9 DIN-rail industrial Circuit breaker ...
[c] ... with adaptable Vigi RCD module
Fig. F49 – Domestic residual current circuit breakers (RCCBs) for earth leakage protection
[a] The incoming-supply circuit breaker can also have time-delayed characteristics and integrate a RCD (type S)
[b] “Monobloc” iID residual current circuit breakers intended for protection of terminal socket-outlet circuits in domestic and tertiary sector applications
Fig. F50 – RCDs with separate toroidal current transformers (Vigirex)
Fig. F78 – Different types of ground fault prodections
Fig. F86 – Situation increasing risks of fire (per-row:4)
Power supply cord subjected to excessive forces (by furniture or a position)
Power supply cord defective following inappropriate or excessively numerous operations
Cable weakened at connection
Accidental damage to a cable
Power sockets in poor condition
Ageing of cable protective devices
Cables damaged by their environment: UV, vibrations, moisture, rodents.
Fig. G7 – Location of protective devices
Fig. H16 – Symbol for a non-automatic switch-fuse
Fig. H26 – Example of air circuit-breakers. Masterpact provides many control features in its “Micrologic” tripping unit
Fig. H36 – Performance curves of a typical LV current-limiting circuit-breaker
Fig. H52 – Current based selectivity, Time based selectivity, Combination of both
Fig. J34 – SCPD "in parallel"
Fig. J35 – SPDs with external SCPD, non-integrated (iC60N + iPRD 40r) and integrated (iQuick PRD 40r)
Fig. J41 – Examples of good and bad SPD installations
Example 1: Equipment installation design should be done in accordance to installation rules: cables length shall be less than 50 cm.
Exemple 2 : Positioning of devices should be linked to installation rules: reduce length of cables < 50 cm and keep the loop area rule of reducing impact of magnetic fields created by lightning current.
Fig. J42 – SPD with separate or integrated external SCPD
Fig. J52 – The Schneider Electric brand iPRD SPD incorporates a gas discharge tube between neutral and earth and varistors between phase and neutral
Fig. K18 – Motor starter examples: TeSys D Direct on line contactors, Star Delta starter, Altistart softstarter (Schneider Electric)
Fig. K19 – Variable Speed Drives of various power ratings (Altivar range, Schneider Electric)
Fig. K22 – A selection of lighting control devices: timers, light sensors, movement sensors (per-row:3)
Fig. L9 – Showing the essential features of power-factor correction
[a] Reactive current components only flow pattern
[b] When IC = IL, all reactive power is supplied from the capacitor bank
[c] With load current added to case (b)
Fig. M9 – Harmonic spectrum for a rectangular signal U(t)
Fig. M13 – Example of electronic trip units of circuit-breakers providing harmonic related information
Fig. N39 – Compact fluorescent lamps
Fig. N47 – Coordination between circuit breaker and luminaires LED (per-row:2)
Fig. N57 – Shape of the voltage supplied by a light dimmer at 50% of maximum voltage with the following techniques:
Fig. N61 – Power supply voltage at switch-on and inrush current (per-row:1)
Fig. N68 – Examples of control devices (Schneider Electric brand)
[a] “zero crossing” contactor iCT+
[b] “standard” contactor iCT
[d] remote controlled MCB
Fig. N81 – The various functions and their combinations forming a motor starter
Fig. P26 – A photovoltaic system can be connected directly to the electrical distribution network (left) or connected to the building electrical installation and used for self-consumption (right).
Solar production exported to the grid
Solar production used for self-consumption
Fig. P37 – Illustration of the current value significant differences between the different operating modes. Example of installation with storage integration
Fig. P46 – Recommended connection of single-phase photovoltaic inverters in a three-phase electrical installation to avoid unbalance
Fig. P48 – Example of electrical installation
with solar production providing active power only (by default)
with solar system with an appropriate set point value of the solar inverters to avoid power factor penalties
Fig. Q5 – Examples of incoming-supply circuit breakers or switch from different countries
[b] UK (switch-disconnector)
Fig. S3 – Examples of products compliant with IEC 61557-12, for Energy Efficiency
Acti9 iEM2000 series energy meters Schneider Electric
Acti9 iEM3000 series energy meters Schneider Electric
Fig. S7 – Examples of products compliant with IEC 61557-12, for Electrical Distribution Monitoring
Compact NSX circuit breaker equipped with a Micrologic trip unit, Schneider Electric
Masterpact MTZ circuit breaker equipped with a Micrologic trip unit, Schneider Electric
PowerLogic PM5000 series power meters, Schneider Electric
PowerLogic PM8000 series power meters, Schneider Electric
Fig. S9 – Examples of products compliant with IEC 61000-4-30 for Grid Power Quality
PowerLogic ION9000
Power Quality Instrument class A (PQI-A)
compliant with IEC 62586-1
Schneider Electric
PowerLogic ION7550/ION7650
Power Quality Device
Schneider Electric
PowerLogic ION8800
Power Quality Device
Schneider Electric
PowerLogic ION8650
Power Quality Device
Schneider Electric
Fig. EV20 – Examples of charging stations