Common characteristics of SPDs according to the installation characteristics
From Electrical Installation Guide
Contents |
Operating voltage Uc
Depending on the system earthing arrangement, the maximum continuous operating voltage Uc of SPD must be equal to or greater than the values shown in the table in Figure J24.
| SPDs connected between | System configuration of distribution network | ||||
| TT | TN-C | TN-S | IT with distributed neutral | IT without distributed neutral | |
| Line conductor and neutral conductor | 1.1 Uo | NA | 1.1 Uo | 1.1 Uo | NA |
| Each line conductor and PE conductor | 1.1 Uo | NA | 1.1 Uo | Uo
| Vo |
| Neutral conductor and PE conductor | Uo | NA | Uo | Uo | NA |
| Each line conductor and PEN conductor | NA | 1.1 Uo | NA | NA | NA |
|
NA: not applicable | |||||
Fig. J24: Stipulated minimum value of Uc for SPDs depending on the system earthing arrangement (based on Table 53C of the IEC 60364-5-53 standard)
The most common values of Uc chosen according to the system earthing arrangement.
TT, TN: 260, 320, 340, 350 V
IT: 440, 460 V
Voltage protection level Up (at In)
The 443-4 section of IEC 60364 standard, “Selection of equipment in the installation”, helps with the choice of the protection level Up for the SPD in function of the loads to be protected. The table of Figure J25 indicates the impulse withstand capability of each kind of equipment.
| Nominal voltage of the installation(1) V | Required impulse withstand voltage for kV | |||||
| Three-phase systems(2) | Single-phase systems with middle point | Equipment at the origin of the installation (impulse withstand category IV) | Equipment of distribution and final circuits (impulse withstand category III) | Appliances(impulse withstand category II) | Specially protected equipment (impulse withstand category I) | |
| 120 - 240 | 4 | 2.5 | 1.5 | 0.8 | ||
|
230/400(2) 277/480(2) | - | 6 | 4 | 2.5 | 1.5 | |
| 400/690 | - | 8 | 6 | 4 | 2.5 | |
| 1,000 | - | Values subject to system engineers | ||||
(1) As per IEC 60038.
(2) In Canada and the United States, for voltages exceeding 300 V relative to earth, the impulse withstand voltage corresponding to the immediately higher voltage in the column is applicable.
(3) This impulse withstand voltage is applicable between live conductors and the PE conductor
Fig. J25: Equipment impulse withstand category for an installation in conformity with IEC 60364 (Table 44B).
Fig. J26: Overvoltage category of equipment
The "installed" Up performance should be compared with the impulse withstand capability of the loads.
SPD has a voltage protection level Up that is intrinsic, i.e. defined and tested independently of its installation. In practice, for the choice of Up performance of a SPD, a safety margin must be taken to allow for the overvoltages inherent in the installation of the SPD (see Fig. J27).
The "installed" voltage protection level Up generally adopted to protect sensitive equipment in 230/400 V electrical installations is 2.5 kV (overvoltage category II, see Fig. J28).
| Note: If the stipulated voltage protection level cannot be achieved by the incoming-end SPD or if sensitive equipment items are remote, additional coordinated SPD must be installed to achieve the required protection level. |
Number of poles
- Depending on the system earthing arrangement, it is necessary to provide for a SPD architecture ensuring protection in common mode (CM) and differential mode (DM).
| TT | TN-C | TN-S | IT | |
| Phase-to-neutral (DM) | Recommended1 | - | Recommended | Not useful |
| Phase-to-earth (PE or PEN) (CM) | Yes | Yes | Yes | Yes |
| Neutral-to-earth (PE) (CM) | Yes | - | Yes | Yes2 |
1 The protection between phase and neutral can either be incorporated in the SPD placed at the origin of the installation, or be remoted close to the equipment to be protected
2 If neutal distributed
Fig. J28: Protection need according to the system earthing arrangement
Note:
- Common-mode overvoltage
A basic form of protection is to install a SPD in common mode between phases and the PE (or PEN) conductor, whatever the type of system earthing arrangement used.
- Differential-mode overvoltage
In the TT and TN-S systems, earthing of the neutral results in an asymmetry due to earth impedances which leads to the appearance of differential-mode voltages, even though the overvoltage induced by a lightning stroke is common-mode.
2P, 3P and 4P SPDs (see Fig. J29)
- These are adapted to the TT and TN-S systems.
- They provide protection merely against common-mode overvoltages.
1P + N, 3P + N SPDs (see Fig. J30)
- These are adapted to the TT and TN-S systems.
- They provide protection against common-mode and differential-mode overvoltages
Uo







