Fig. E1 – An example of a block of flats in which the main earthing terminal (6) provides the main equipotential connection; the removable link (7) allows an earth-electrode-resistance check (DB422160_EN)
Fig. E25 – Measurement of the resistance to earth of the earth electrode of an installation by means of an ammeter (DB422180)
Fig. E26 – Measurement of the resistance to the mass of earth of electrode (X) using an earth-electrode-testing ohmmeter (DB422181a_EN)
Fig. E26 – Measurement of the resistance to the mass of earth of electrode (X) using an earth-electrode-testing ohmmeter (DB422181b)

Fig. E27 – [a] A main LV switchboard - MLVS - (Prisma Plus P) with incoming circuits in the form of busways - [b] A LV motor control centre - MCC - (Okken) (PB116715)

Fig. E27 – [a] A main LV switchboard - MLVS - (Prisma Plus P) with incoming circuits in the form of busways - [b] A LV motor control centre - MCC - (Okken) (PB116716)

Fig. E29 – Final distribution switchboards [a] Prisma Plus G Pack; [b] Kaedra; [c] mini-Pragma (PB116718)

Fig. E29 – Final distribution switchboards [a] Prisma Plus G Pack; [b] Kaedra; [c] mini-Pragma (PB116719)

Fig. E29 – Final distribution switchboards [a] Prisma Plus G Pack; [b] Kaedra; [c] mini-Pragma (PB116720)

Fig. E30 – Assembly of a final distribution switchboard with fixed functional units (Prisma Plus G) (PB116721)
Fig. E32b – Main actors and responsibilities, as defined by the IEC 61439-1&2 standard (DB422182_EN)
Fig. E33 – Representation of different forms of LV functional distribution switchboards (DB422183_EN)
Fig. E37 – Busbar trunking system design for distribution of currents from 25 to 4000 A (DB422201_EN)
Fig. E39 – Example of a set of 14 x 25A loads distributed along 34 meters (for busway, Canalis KS 250A) (DB422186_EN)

Fig. E41 – Rigid busbar trunking able to support light fittings: Canalis KBA or KBB (25 and 40 A) (PB116726)
Fig. E47 – Line and neutral currents absorbed by single-phase non-linear loads connected between phase and neutral. (DB422188)

Fig. E48 – Examples of applications where the level of harmonics (THD) is either negligible or high, depending on the proportion of loads generating harmonics versus classical loads. (PB116730)

Fig. E48 – Examples of applications where the level of harmonics (THD) is either negligible or high, depending on the proportion of loads generating harmonics versus classical loads. (PB116731)
Fig. E50 – Typical harmonic neutral current spectrum for single-phase non-linear loads (DB422190_EN)
Fig. E53 – Double-neutral installation for cable solution is not directly applicable for busway solution, due to their very different thermal dissipation behaviour. (DB422193)
Fig. E54 – Illustration of the overheating risk with standard busway sizing in presence of high level of 3rd harmonics (DB422194_EN)
Fig. E56 – The most effective solution = reduce the current density in ALL conductors, by selecting proper busway rating (single-neutral) (DB422196)
Fig. E58 – Comparison between double-neutral busway solution and properly selected single-neutral solution (DB422198a_EN)








