DB422220_EN - F1
AC-1 zone: Imperceptible
AC-2 zone: Perceptible
AC-3 zone: Reversible effects: muscular contraction
AC-4 zone: Possibility of irreversible effects
AC-4-1 zone: Up to 5% probability of heart fibrillation
AC-4-2 zone: Up to 50% probability of heart fibrillation
AC-4-3 zone: More than 50% probability of heart fibrillation
A curve: Threshold of perception of current
B curve: Threshold of muscular reactions
C1 curve: Threshold of 0% probability of ventricular fibrillation
C2 curve: Threshold of 5% probability of ventricular fibrillation
C3 curve: Threshold of 50% probability of ventricular fibrillation
AC-2 zone: Perceptible
AC-3 zone: Reversible effects: muscular contraction
AC-4 zone: Possibility of irreversible effects
AC-4-1 zone: Up to 5% probability of heart fibrillation
AC-4-2 zone: Up to 50% probability of heart fibrillation
AC-4-3 zone: More than 50% probability of heart fibrillation
A curve: Threshold of perception of current
B curve: Threshold of muscular reactions
C1 curve: Threshold of 0% probability of ventricular fibrillation
C2 curve: Threshold of 5% probability of ventricular fibrillation
C3 curve: Threshold of 50% probability of ventricular fibrillation
Fig. F1 – Zones time/current of effects of AC current on human body when passing from left hand to feet
DB422221_EN - F2
DB422222_EN - F3
DB422223 - F4
PB116740 - F5
PB116741 - F6
DB422224_EN - F7
DB422225_EN - F9
DB422226_EN - F12
DB422227_EN - F14
DB422228_EN - F15
PB116742 - F16
DB422229_EN - F17
DB422230_EN - F18
DB422231_EN - F20
DB422232 - F21
DB422233 - F22
DB422234_EN - F23
DB422235_EN - F24
DB422236_EN - F25
DB422237_EN - F26
DB422239_EN - F29
DB422240_EN - F30
DB422241 - F31
DB422242_EN - F32
DB422243 - F33
DB422244_EN - F34
DB422245_EN - F35
DB422246_EN - F36
DB422247_EN - F37
DB422248_EN - F38
Notes:
- The TN scheme requires that the LV neutral of the MV/LV transformer, the exposed conductive parts of the substation and of the installation, and the extraneous conductive parts in the substation and installation, all be earthed to a common earthing system.
- For a substation in which the metering is at low-voltage, a means of isolation is required at the origin of the LV installation, and the isolation must be clearly visible.
- A PEN conductor must never be interrupted under any circumstances.
Control and protective switchgear for the several TN arrangements will be:
- 3-pole when the circuit includes a PEN conductor,
- Preferably 4-pole (3 phases + neutral) when the circuit includes a neutral with a separate PE conductor.
- The TN scheme requires that the LV neutral of the MV/LV transformer, the exposed conductive parts of the substation and of the installation, and the extraneous conductive parts in the substation and installation, all be earthed to a common earthing system.
- For a substation in which the metering is at low-voltage, a means of isolation is required at the origin of the LV installation, and the isolation must be clearly visible.
- A PEN conductor must never be interrupted under any circumstances.
Control and protective switchgear for the several TN arrangements will be:
- 3-pole when the circuit includes a PEN conductor,
- Preferably 4-pole (3 phases + neutral) when the circuit includes a neutral with a separate PE conductor.
Fig. F38 – Implementation of the TN system of earthing