DB422220_EN - F1
AC-1 zone: Imperceptible
AC-2 zone: Perceptible
AC-3 zone: Reversible effects: muscular contraction
AC-4 zone: Possibility of irreversible effects
AC-4-1 zone: Up to 5% probability of heart fibrillation
AC-4-2 zone: Up to 50% probability of heart fibrillation
AC-4-3 zone: More than 50% probability of heart fibrillation
A curve: Threshold of perception of current
B curve: Threshold of muscular reactions
C1 curve: Threshold of 0% probability of ventricular fibrillation
C2 curve: Threshold of 5% probability of ventricular fibrillation
C3 curve: Threshold of 50% probability of ventricular fibrillation
AC-2 zone: Perceptible
AC-3 zone: Reversible effects: muscular contraction
AC-4 zone: Possibility of irreversible effects
AC-4-1 zone: Up to 5% probability of heart fibrillation
AC-4-2 zone: Up to 50% probability of heart fibrillation
AC-4-3 zone: More than 50% probability of heart fibrillation
A curve: Threshold of perception of current
B curve: Threshold of muscular reactions
C1 curve: Threshold of 0% probability of ventricular fibrillation
C2 curve: Threshold of 5% probability of ventricular fibrillation
C3 curve: Threshold of 50% probability of ventricular fibrillation
Fig. F1 – Zones time/current of effects of AC current on human body when passing from left hand to feet
DB422221_EN - F2
DB422222_EN - F3
DB422223 - F4
Fig. F4 – Inherent protection against direct contact by insulation of a 3-phase cable with outer sheath
PB116740 - F5
PB116741 - F6
DB422224_EN - F7
DB422225_EN - F9
DB422226_EN - F12
DB422227_EN - F14
DB422228_EN - F15
PB116742 - F16
DB422229_EN - F17
DB422230_EN - F18
Fig. F18 – Circuit breaker tripping on double fault situation when exposed-conductive-parts are connected to a common protective conductor
DB422231_EN - F20
Fig. F20 – Application of RCDs when exposed-conductive-parts are earthed individually or by group on IT system
DB422232 - F21
DB422233 - F22
DB422234_EN - F23
DB422235_EN - F24
Fig. F24 – Protection by out-of arm’s reach arrangements and the interposition of non-conducting obstacles
DB422236_EN - F25
DB422237_EN - F26
Some tests have shown that a very low leakage current (a few mA) can evolve and, from 300 mA, induce a fire in humid and dusty environment.
Fig. F26 – Origin of fires in buildings
DB422239_EN - F29
DB422240_EN - F30
DB422241 - F31
DB422242_EN - F32
DB422243 - F33
DB422244_EN - F34
DB422245_EN - F35
DB422246_EN - F36
DB422247_EN - F37
Fig. F37 – Typical 3-level installation, showing the protection of distribution circuits in a TT-earthed system. One motor is provided with specific protection
DB422248_EN - F38
Notes:
- The TN scheme requires that the LV neutral of the MV/LV transformer, the exposed conductive parts of the substation and of the installation, and the extraneous conductive parts in the substation and installation, all be earthed to a common earthing system.
- For a substation in which the metering is at low-voltage, a means of isolation is required at the origin of the LV installation, and the isolation must be clearly visible.
- A PEN conductor must never be interrupted under any circumstances.
Control and protective switchgear for the several TN arrangements will be:
- 3-pole when the circuit includes a PEN conductor,
- Preferably 4-pole (3 phases + neutral) when the circuit includes a neutral with a separate PE conductor.
- The TN scheme requires that the LV neutral of the MV/LV transformer, the exposed conductive parts of the substation and of the installation, and the extraneous conductive parts in the substation and installation, all be earthed to a common earthing system.
- For a substation in which the metering is at low-voltage, a means of isolation is required at the origin of the LV installation, and the isolation must be clearly visible.
- A PEN conductor must never be interrupted under any circumstances.
Control and protective switchgear for the several TN arrangements will be:
- 3-pole when the circuit includes a PEN conductor,
- Preferably 4-pole (3 phases + neutral) when the circuit includes a neutral with a separate PE conductor.
Fig. F38 – Implementation of the TN system of earthing
DB422249 - F39
DB422240_EN - F45
DB422241 - F46
DB422242_EN - F47
DB422250_EN - F48
DB422251_EN - F49
DB422252_EN - F50
DB422253_EN - F52
DB422254 - F53
DB422255_EN - F54
DB422256 - F55
DB422257_EN - F56
Fig. F56 – Calculation of Lmax. for an IT-earthed system, showing fault-current path for a double-fault condition
DB422267 - F58
DB422258_EN - F59
DB422259_EN - F60
DB422251_EN - F61
DB422252_EN - F62
DB422260 - F63
DB422261_EN - F67
DB422262_EN - F68
DB422263_EN - F69
DB422264 - F73
L = twice the diameter of the magnetic ring core
Fig. F73 – Means of reducing the ratio IΔn/Iph (max.)






