Talk:Recommended simplified approach for cable sizing

From Electrical Installation Guide

About this board

Not editable

Jjjooonnn (talkcontribs)

I believe the A1, 3 PVC column (14.5 Amps) should be: A1, 2 PVC column (13.5 Amps)

See: IEC 60364 Part 5-52 Table B.52.2 (Two-Loaded Conductors) IEC 60364 Part 5-52 Table B.52.4 (Three-Loaded Conductors)

There are no older topics