TT system - Coordination of residual current protective devices

From Electrical Installation Guide

Jump to: navigation, search
Scope and content of Wiki EIG
General rules of electrical installation design
Connection to the MV utility distribution network
Connection to the LV utility distribution network
MV & LV architecture selection guide
LV Distribution
Protection against electric shocks
Sizing and protection of conductors
LV switchgear: functions & selection
Protection against voltage surges in LV
Energy Efficiency in electrical distribution
Power factor correction and harmonic filtering
Power harmonics management
Characteristics of particular sources and loads
PhotoVoltaic (PV) installation
Residential electrical installations
ElectroMagnetic Compatibility (EMC)


Contents


Discriminative-tripping coordination is achieved either by time-delay or by subdivision of circuits, which are then protected individually or by groups, or by a combination of both methods.
Such discrimination avoids the tripping of any RCD, other than that immediately upstream of a fault position:

  • With equipment currently available, discrimination is possible at three or four different levels of distribution :

  - At the main general distribution board
  - At local general distribution boards
  - At sub-distribution boards
  - At socket outlets for individual appliance protection

  • In general, at distribution boards (and sub-distribution boards, if existing) and on individual-appliance protection, devices for automatic disconnection in the event of an indirect-contact hazard occurring are installed together with additional protection against direct-contact hazards.

Discrimination between RCDs

The general specification for achieving total discrimination between two RCDs is as follow:

  • The ratio between the rated residual operating currents must be > 2
  • Time delaying the upstream RCD

Discrimination is achieved by exploiting the several levels of standardized sensitivity: 30 mA, 100 mA, 300 mA and 1 A and the corresponding tripping times, as shown in Figure F34.



FigF34.jpg





















Fig. F34: Total discrimination at 2 levels


Discrimination at 2 levels

(see Fig. F35)
Protection

  • Level A: RCD time-delayed setting I (for industrial device) or type S (for domestic device) for protection against indirect contacts
  • Level B: RCD instantaneous, with high sensitivity on circuits supplying socket-outlets or appliances at high risk (washing machines, etc.)

Schneider Electric solutions

  • Level A: Compact or Multi 9 circuit-breaker with adaptable RCD module (Vigi NSX160 or Vigi NC100), setting I or S type
  • Level B: Circuit-breaker with integrated RCD module (DPN Vigi) or adaptable RCD module (e.g. Vigi C60 or Vigi NC100) or Vigicompact

Note: The setting of upstream RCCB must comply with selectivity rules and take into account all the downstream earth leakage currents.



FigF35.jpg










Fig. F35: Total discrimination at 2 levels

Discrimination at 3 or 4 levels

(see Fig. F36)
Protection

  • Level A: RCD time-delayed (setting III)
  • Level B: RCD time-delayed (setting II)
  • Level C: RCD time-delayed (setting I) or type S
  • Level D: RCD instantaneous

Schneider Electric solutions

  • Level A: Circuit-breaker associated with RCD and separate toroidal transformer (Vigirex RH328AP)
  • Level B: Vigicompact or Vigirex
  • Level C: Vigirex, Vigicompact or Vigi NC100 or Vigi C60
  • Level D:

  - Vigicompact or
  - Vigirex or
  - Multi 9 with integrated or adaptable RCD module: Vigi C60 or DPN Vigi
Note: The setting of upstream RCCB must comply with selectivity rules and take into account all the downstream earth leakage currents



FigF36.jpg



















Fig. F36: Total discrimination at 3 or 4 levels

Discriminative protection at three levels (see Fig. F37)



FigF37.jpg










































Fig. F37: Typical 3-level installation, showing the protection of distribution circuits in a TT-earthed system. One motor is provided with specific protection