TN system - High-sensitivity RCDs

From Electrical Installation Guide

Jump to: navigation, search
Scope and content of Wiki EIG
General rules of electrical installation design
Connection to the MV utility distribution network
Connection to the LV utility distribution network
MV & LV architecture selection guide
LV Distribution
Protection against electric shocks
Sizing and protection of conductors
LV switchgear: functions & selection
Protection against voltage surges in LV
Energy Efficiency in electrical distribution
Power factor correction and harmonic filtering
Power harmonics management
Characteristics of particular sources and loads
PhotoVoltaic (PV) installation
Residential electrical installations
ElectroMagnetic Compatibility (EMC)


(see Fig. F46)
According to IEC 60364-4-41, high sensitivity RCDs (≤ 30 mA) must be used for protection of socket outlets with rated current ≤ 20 A in all locations. The use of such RCDs is also recommended in the following cases:

  • Socket-outlet circuits in wet locations at all current ratings
  • Socket-outlet circuits in temporary installations
  • Circuits supplying laundry rooms and swimming pools
  • Supply circuits to work-sites, caravans, pleasure boats, and travelling fairs 


FigF46.jpg
 











Fig. F46: Circuit supplying socket-outlets