Protection of LV/LV transformers, using Merlin Gerin circuit-breakers

From Electrical Installation Guide

Jump to: navigation, search
Scope and content of Wiki EIG
General rules of electrical installation design
Connection to the MV utility distribution network
Connection to the LV utility distribution network
MV & LV architecture selection guide
LV Distribution
Protection against electric shocks
Sizing and protection of conductors
LV switchgear: functions & selection
Protection against voltage surges in LV
Energy Efficiency in electrical distribution
Power factor correction and harmonic filtering
Power harmonics management
Characteristics of particular sources and loads
PhotoVoltaic (PV) installation
Residential electrical installations
ElectroMagnetic Compatibility (EMC)





Multi 9 circuit-breaker 

Transformer power rating (kVA) Cricuit breaker Size
230/240 V 1-ph 230/240 V 3-ph
400/415 V 1-ph
400/415 V 3-ph curve D or K (A)
0.05 0.09 0.16 C60, NG125 0.5
0.11 0.18 0.32 C60, NG125 1
0.21 0.36 .063 C60, NG125 2
0.33 0.58 1.0 C60, NG125 3
0.67 1.2 2.0 C60, NG125 6
1.1 1.8 3.2 C60, C120, NG125 10
1.7 2.9 5.0 C60, C120, NG125 16
2.1 3.6 6.3 C60, C120, NG125 20
2.7 4.6 8.0 C60, C120, NG125 25
3.3 5.8 10 C60, C120, NG125 32
4.2 7.2 13 C60, C120, NG125 40
5.3 9.2 16 C60, C120, NC100, NG125 50
6.7 12 20 C60, C120, NC100, NG125 63
8.3 14 25 C120, NC100, NG125 80
11 18 32 C120, NC100, NG125 100
13 23 40 C120, NG125 125

 
Compact NS100…NS250 circuit-breakers with TM-D trip unit

Transformer power rating (kVA) Circuit-breaker Trip unit
230/240 V 1-ph 230/240 V 3-ph
400/415 V 1-ph
400/415 V 3-ph
3 5...6 9...12 NS100N/H/L TN16D
5 8...9 14...16 NS100N/H/L TM05D
7...9 13...16 22...28 NS100N/H/L TN40D
12...15 20...25 35...44 NS100N/H/L TN63D
16...19 26...32 45...56 NS100N/H/L TN80D
18...23 32...40 55...69 NS160N/H/L TN100D
23...29 40...50 69...87 NS160N/H/L TN125D
29...37 51...64 89...111 NS250N/H/L TN160D
37...46 64...80 111...139 NS250N/H/L TN200D


Compact NS100…NS1600 and Masterpact circuit-breakers with STR or Micrologic trip unit

Transformer power rating (kVA) Circuit-breaker Trip unit Setting
Ir max
230/240 V 1-ph 230/240 V 3-ph
400/415 V 1-ph
400/415 V 3-ph
4...7 6...13 11...22 NS100N/H/L STR22SE 40 0.8
9...19 16...30 27...56 NS100N/H/L STR22SE 100 0.8
15...30 5...50 44...90 NS160N/H/L STR22SE 160 0.8
23...46 40...80 70...139 NS250N/H/L STR22SE 250 0.8
37...65 64...112 111...195 NS400N/H STR23SE / 53UE 400 0.7
37...55 64...95 111...166 NS400L STR23SE / 53UE 400 0.6
58...83 100...144 175...250 NS630N/H/L STR23SE / 53UE 630 0.6
58...150 100...250 175...436 NS800N/H - NT08H1 Micrologic 5.0/6.0/7.0 1
74...184 107...319 222...554 NS800N/H - NT08H1 - NW08N1/H1 Micrologic 5.0/6.0/7.0 1
90...230 159...398 277...693 NS1000N/H - NT10H1 - NW10N1/H1 Micrologic 5.0/6.0/7.0 1
115...288 200...498 346...866 NS1250N/H - NT12H1 - NW12N1/H1 Micrologic 5.0/6.0/7.0 1
147...368 256...640 443...1,108 NS1600N/H - NT16H1 - NW16N1/H1 Micrologic 5.0/6.0/7.0 1
184...460 320...800 554...1,385 NW20N1/H1 Micrologic 5.0/6.0/7.0 1
230...575 400...1, 000 690...1,730 NW25N2/H3 Micrologic 5.0/6.0/7.0 1
294...736 510...1,280 886...2,217 NW32N2/H3 Micrologic 5.0/6.0/7.0 1