Power values and harmonics

From Electrical Installation Guide

Jump to: navigation, search
Scope and content of Wiki EIG
General rules of electrical installation design
Connection to the MV utility distribution network
Connection to the LV utility distribution network
MV & LV architecture selection guide
LV Distribution
Protection against electric shocks
Sizing and protection of conductors
LV switchgear: functions & selection
Protection against voltage surges in LV
Energy Efficiency in electrical distribution
Power factor correction and harmonic filtering
Power harmonics management
Characteristics of particular sources and loads
PhotoVoltaic (PV) installation
Residential electrical installations
ElectroMagnetic Compatibility (EMC)

Contents


Active power

The active power P of a signal comprising harmonics is the sum of the active powers resulting from the currents and voltages of the same order.

Reactive power

Reactive power is defined exclusively in terms of the fundamental, i.e.
Q=U1 \times I1 \times Sin \phi 1

Distortion power

When harmonics are present, the distortion power D is defined as
D= \left(S^2 - P^2 -Q^2 \right)^{1/2} where S is the apparent power.