IT system - Preliminary conditions
From Electrical Installation Guide
(see Fig. F51 and Fig. F52 )
| Minimum functions required | Components and devices | Examples |
| Protection against overvoltages at power frequency | (1) Voltage limiter | Cardew C |
| Neutral earthing resistor (for impedance earthing variation) | (2) Resistor | Impedance Zx |
| Overall earth-fault monitor with alarm for first fault condition | (3) Permanent insulation monitor PIM with alarm feature | Vigilohm TR22A or XM 200 |
| Automatic fault clearance on second fault and protection of the neutral conductor against overcurrent | (4) Four-pole circuit-breakers (if the neutral is distributed) all 4 poles trip | Compact circuit-breaker or RCD-MS |
| Location of first fault | (5) With device for fault-location on live system, or by successive opening of circuits | Vigilohm system |
Fig. F51: Essential functions in IT schemes and examples with Merlin Gerin products
Fig. F52: Positions of essential functions in 3-phase 3-wire IT-earthed system