Different type of ground fault protections

(see Fig. F27)

Three types of GFP are possible dependind on the measuring device installed :

  • “Residual Sensing” RS

The “insulation fault” current is calculated using the vectorial sum of currents of current transformers secondaries. The current transformer on the neutral conductor is often outside the circuit-breaker.

  • “Source Ground Return” SGR

The « insulation fault current » is measured in the neutral – earth link of the LV transformer. The current transformer is outside the circuit-breaker. 

  • “Zero Sequence” ZS

The « insulation fault » is directly measured at the secondary of the current transformer using the sum of currents in live conductors. This type of GFP is only used with low fault current values.



FigF27.jpg















Fig. F27: Different types of ground fault protections

Positioning GFP devices in the installation

Type / installation level Main-distribution Sub-distribution Comments
Source Ground Return (SGR)   Used
Residual Sensing (RS) (SGR)   Often used
Zero Sequence (SGR) Rarely used

Possible
Recommended or required