Choosing the optimum solution for power-system harmonics

From Electrical Installation Guide

Jump to: navigation, search
Scope and content of Wiki EIG
General rules of electrical installation design
Connection to the MV utility distribution network
Connection to the LV utility distribution network
MV & LV architecture selection guide
LV Distribution
Protection against electric shocks
Sizing and protection of conductors
LV switchgear: functions & selection
Protection against voltage surges in LV
Energy Efficiency in electrical distribution
Power factor correction and harmonic filtering
Power harmonics management
Characteristics of particular sources and loads
PhotoVoltaic (PV) installation
Residential electrical installations
ElectroMagnetic Compatibility (EMC)


Figure L31 below shows the criteria that can be taken into account to select the most suitable technology depending on the application.



   Passive filter Active filter Hybrid filter
Applications
… with total power of non linear loads
(variable speed drive, UPS, rectifier…)
Industrial Tertiary Industrial
greater than
200 kVA
lower than
200 kVA
greater than 
200 kVA
Power factor correction     No   
Necessity of reducing the harmonic distorsion in voltage for sensitive loads            
Necessity of reducing the harmonic distorsion in current to avoid cable overload         
Necessity of being in accordance with strict limits of harmonic rejected No      

Fig. L31: Selection of the most suitable technology depending on the application


For passive filter, a choice is made from the following parameters:

  • Gh = the sum of the kVA ratings of all harmonic-generating devices (static converters, inverters, speed controllers, etc.) connected to the busbars from which the capacitor bank is supplied. If the ratings of some of these devices are quoted in kW only, assume an average power factor of 0.7 to obtain the kVA ratings
  • Ssc = the 3-phase short-circuit level in kVA at the terminals of the capacitor bank
  • Sn = the sum of the kVA ratings of all transformers supplying (i.e. directly connected to) the system level of which the busbars form a part

If a number of transformers are operating in parallel, the removal from service of one or more, will significantly change the values of Ssc and Sn. From these parameters, a choice of capacitor specification which will ensure an acceptable level of operation with the system harmonic voltages and currents, can be made, by reference to Figure L32.



  • General rule valid for any size of transformer
                     
Standard capacitors Capacitor voltage rating increased by 10% (except 230 V units)  Capacitor voltage rating increased by 10% + harmonic-suppression
reactor  
  • Simplified rule if transformer(s) rating Sn ≤ 2 MVA
       Gh > 0.60Sn              
Standard capacitors Capacitor voltage rating increased by 10% (except 230 V units) Capacitor voltage rating increased by 10%  + harmonic suppression reactor Filters

Fig. L32: Choice of solutions for limiting harmonics associated with a LV capacitor bank supplied via transformer(s)

Personal tools