Calculation of voltage drop in steady load conditions
From Electrical Installation Guide
Contents |
Use of formulae
Figure G27 below gives formulae commonly used to calculate voltage drop in a given circuit per kilometre of length.
If:
- IB: The full load current in amps
- L: Length of the cable in kilometres
- R: Resistance of the cable conductor in Ω/km
for copper
for aluminium
Note: R is negligible above a c.s.a. of 500 mm2
- X: inductive reactance of a conductor in Ω/km
Note: X is negligible for conductors of c.s.a. less than 50 mm2. In the absence of any other information, take X as being equal to 0.08 Ω/km.
- ϕ: phase angle between voltage and current in the circuit considered, generally:
- Incandescent lighting: cosφ = 1
- Motor power:
- At start-up: cosφ = 0.35
- In normal service: cosφ = 0.8
- Un: phase-to-phase voltage
- Vn: phase-to-neutral voltage
For prefabricated pre-wired ducts and bustrunking, resistance and inductive reactance values are given by the manufacturer.
| Circuit | Voltage drop (ΔU) | |
| in volts | in % | |
| Single phase: phase/phase |
|
|
| Single phase: phase/neutral |
|
|
| Balanced 3-phase: 3 phases (with or without neutral) |
|
|
Fig. G27: Voltage-drop formulae
Simplified table
Calculations may be avoided by using Figure G28, which gives, with an adequate approximation, the phase-to-phase voltage drop per km of cable per ampere, in terms of:
- Kinds of circuit use: motor circuits with cosφclose to 0.8, or lighting with a cosφclose to 1.
- Type of cable; single-phase or 3-phase
Voltage drop in a cable is then given by:
K x IB x L
K is given by the table,
IB is the full-load current in amps,
L is the length of cable in km.
The column motor power “cosφ = 0.35” of Figure G28 may be used to compute the voltage drop occurring during the start-up period of a motor (see example no. 1 after the Figure G28).
| c.s.a. in mm2 | Single-phase circuit | Balanced three-phase circuit | |||||
| Motor power | Lighting | Motor power | Lighting | ||||
| Normal service | Start-up | Normal service | Start-up | ||||
| Cu | AI | cos φ = 0.8 | cos φ = 0.35 | cos φ = 1 | cos φ = 0.8 | cos φ = 0.35 | cos φ = 1 |
| 1.5 | 24 | 10.6 | 30 | 20 | 9.4 | 25 | |
| 2.5 | 14.4 | 6.4 | 18 | 12 | 5.7 | 15 | |
| 4 | 9.1 | 4.1 | 11.2 | 8 | 3.6 | 9.5 | |
| 6 | 10 | 6.1 | 2.9 | 7.5 | 5.3 | 2.5 | 6.2 |
| 10 | 16 | 3.7 | 1.7 | 4.5 | 3.2 | 1.5 | 3.6 |
| 16 | 25 | 2.36 | 1.15 | 2.8 | 2.05 | 1 | 2.4 |
| 25 | 35 | 1.5 | 0.75 | 1.8 | 1.3 | 0.65 | 1.5 |
| 35 | 50 | 1.15 | 0.6 | 1.29 | 1 | 0.52 | 1.1 |
| 50 | 70 | 0.86 | 0.47 | 0.95 | 0.75 | 0.41 | 0.77 |
| 70 | 120 | 0.64 | 0.37 | 0.64 | 0.56 | 0.32 | 0.55 |
| 95 | 150 | 0.48 | 0.30 | 0.47 | 0.42 | 0.26 | 0.4 |
| 120 | 185 | 0.39 | 0.26 | 0.37 | 0.34 | 0.23 | 0.31 |
| 150 | 240 | 0.33 | 0.24 | 0.30 | 0.29 | 0.21 | 0.27 |
| 185 | 300 | 0.29 | 0.22 | 0.24 | 0.25 | 0.19 | 0.2 |
| 240 | 400 | 0.24 | 0.2 | 0.19 | 0.21 | 0.17 | 0.16 |
| 300 | 500 | 0.21 | 0.19 | 0.15 | 0.18 | 0.16 | 0.13 |
Fig. G28: Phase-to-phase voltage drop ΔU for a circuit, in volts per ampere per km
Examples
Example 1 (see Fig. G29)
A three-phase 35 mm2 copper cable 50 metres long supplies a 400 V motor taking:
- 100 A at a cos φ = 0.8 on normal permanent load
- 500 A (5 In) at a cos φ = 0.35 during start-up
The voltage drop at the origin of the motor cable in normal circumstances (i.e. with the distribution board of Figure G29 distributing a total of 1,000 A) is 10 V phase-to-phase.
What is the voltage drop at the motor terminals:
- In normal service?
- During start-up?
Solution:
- Voltage drop in normal service conditions:
Table G28 shows 1 V/A/km so that:
ΔU for the cable = 1 x 100 x 0.05 = 5 V
ΔU total = 10 + 5 = 15 V = i.e.
This value is less than that authorized (8%) and is satisfactory.
- Voltage drop during motor start-up:
Δ Ucable = 0.52 x 500 x 0.05 = 13 V
Owing to the additional current taken by the motor when starting, the voltage drop at the distribution board will exceed 10 Volts.
Supposing that the infeed to the distribution board during motor starting is 900 + 500 = 1,400 A then the voltage drop at the distribution board will increase approximately pro rata, i.e.
ΔU distribution board = 14 V
ΔU for the motor cable = 13 V
ΔU total = 13 + 14 = 27 V i.e. 
a value which is satisfactory during motor starting.
Fig. G29: Example 1
Example 2 (see Fig. G30)
A 3-phase 4-wire copper line of 70 mm2 c.s.a. and a length of 50 m passes a current of 150 A. The line supplies, among other loads, 3 single-phase lighting circuits, each of 2.5 mm2 c.s.a. copper 20 m long, and each passing 20 A.
It is assumed that the currents in the 70 mm2 line are balanced and that the three lighting circuits are all connected to it at the same point.
What is the voltage drop at the end of the lighting circuits?
Solution:
- Voltage drop in the 4-wire line:
Figure G28 shows 0.55 V/A/km
ΔU line = 0.55 x 150 x 0.05 = 4.125 V phase-to-phase
which gives:
phase to neutral.
- Voltage drop in any one of the lighting single-phase circuits:
ΔU for a single-phase circuit = 18 x 20 x 0.02 = 7.2 V
The total voltage drop is therefore
7.2 + 2.38 = 9.6 V
This value is satisfactory, being less than the maximum permitted voltage drop of 6%.
Fig. G30: Example 2


