Calculation of voltage drop in steady load conditions

From Electrical Installation Guide

Jump to: navigation, search
Scope and content of Wiki EIG
General rules of electrical installation design
Connection to the MV utility distribution network
Connection to the LV utility distribution network
MV & LV architecture selection guide
LV Distribution
Protection against electric shocks
Sizing and protection of conductors
LV switchgear: functions & selection
Protection against voltage surges in LV
Energy Efficiency in electrical distribution
Power factor correction and harmonic filtering
Power harmonics management
Characteristics of particular sources and loads
PhotoVoltaic (PV) installation
Residential electrical installations
ElectroMagnetic Compatibility (EMC)


Contents

Use of formulae

Figure G27 below gives formulae commonly used to calculate voltage drop in a given circuit per kilometre of length.
If:

  • IB: The full load current in amps
  • L: Length of the cable in kilometres
  • R: Resistance of the cable conductor in Ω/km

 for copper

 for aluminium
Note: R is negligible above a c.s.a. of 500 mm2

  • X: inductive reactance of a conductor in Ω/km

Note: X is negligible for conductors of c.s.a. less than 50 mm2. In the absence of any other information, take X as being equal to 0.08 Ω/km.

  • ϕ: phase angle between voltage and current in the circuit considered, generally:

- Incandescent lighting: cosφ = 1
- Motor power:
   - At start-up: cosφ = 0.35
   - In normal service: cosφ = 0.8

  • Un: phase-to-phase voltage
  • Vn: phase-to-neutral voltage

For prefabricated pre-wired ducts and bustrunking, resistance and inductive reactance values are given by the manufacturer.



Circuit Voltage drop (ΔU)
in volts in %
Single phase: phase/phase
Single phase: phase/neutral
Balanced 3-phase: 3 phases (with or without neutral)












Fig. G27: Voltage-drop formulae


Simplified table

Calculations may be avoided by using Figure G28, which gives, with an adequate approximation, the phase-to-phase voltage drop per km of cable per ampere, in terms of:

  • Kinds of circuit use: motor circuits with cosφclose to 0.8, or lighting with a cosφclose to 1.
  • Type of cable; single-phase or 3-phase

Voltage drop in a cable is then given by:
K x IB x L
K is given by the table,
IB is the full-load current in amps,
L is the length of cable in km.
The column motor power “cosφ = 0.35” of Figure G28 may be used to compute the voltage drop occurring during the start-up period of a motor (see example no. 1 after the Figure G28).



c.s.a. in mm2 Single-phase circuit Balanced three-phase circuit
Motor power Lighting Motor power Lighting
Normal service Start-up   Normal service Start-up  
Cu AI cos φ = 0.8 cos φ = 0.35 cos φ = 1 cos φ = 0.8 cos φ = 0.35 cos φ = 1
1.5   24 10.6 30 20 9.4 25
2.5   14.4 6.4 18 12 5.7 15
4   9.1 4.1 11.2 8 3.6 9.5
6 10 6.1 2.9 7.5 5.3 2.5 6.2
10 16 3.7 1.7 4.5 3.2 1.5 3.6
16 25 2.36 1.15 2.8 2.05 1 2.4
25 35 1.5 0.75 1.8 1.3 0.65 1.5
35 50 1.15 0.6 1.29 1 0.52 1.1
50 70 0.86 0.47 0.95 0.75 0.41 0.77
70 120 0.64 0.37 0.64 0.56 0.32 0.55
95 150 0.48 0.30 0.47 0.42 0.26 0.4
120 185 0.39 0.26 0.37 0.34 0.23 0.31
150 240 0.33 0.24 0.30 0.29 0.21 0.27
185 300 0.29 0.22 0.24 0.25 0.19 0.2
240 400 0.24 0.2 0.19 0.21 0.17 0.16
300 500 0.21 0.19 0.15 0.18 0.16 0.13

Fig. G28: Phase-to-phase voltage drop ΔU for a circuit, in volts per ampere per km


Examples

Example 1 (see Fig. G29)
A three-phase 35 mm2 copper cable 50 metres long supplies a 400 V motor taking:

  • 100 A at a cos φ = 0.8 on normal permanent load
  • 500 A (5 In) at a cos φ = 0.35 during start-up

The voltage drop at the origin of the motor cable in normal circumstances (i.e. with the distribution board of Figure G29 distributing a total of 1,000 A) is 10 V phase-to-phase.
What is the voltage drop at the motor terminals:

  • In normal service?
  • During start-up?

Solution:

  • Voltage drop in normal service conditions: 

Table G28 shows 1 V/A/km so that:
ΔU for the cable = 1 x 100 x 0.05 = 5 V
ΔU total = 10 + 5 = 15 V = i.e. 

This value is less than that authorized (8%) and is satisfactory.

  • Voltage drop during motor start-up:

Δ Ucable = 0.52 x 500 x 0.05 = 13 V
Owing to the additional current taken by the motor when starting, the voltage drop at the distribution board will exceed 10 Volts.
Supposing that the infeed to the distribution board during motor starting is 900 + 500 = 1,400 A then the voltage drop at the distribution board will increase approximately pro rata, i.e. 

ΔU distribution board = 14 V
ΔU for the motor cable = 13 V
ΔU total = 13 + 14 = 27 V i.e. 

a value which is satisfactory during motor starting.




FigG29.jpg



























Fig. G29: Example 1

Example 2 (see Fig. G30)
A 3-phase 4-wire copper line of 70 mm2 c.s.a. and a length of 50 m passes a current of 150 A. The line supplies, among other loads, 3 single-phase lighting circuits, each of 2.5 mm2 c.s.a. copper 20 m long, and each passing 20 A.
It is assumed that the currents in the 70 mm2 line are balanced and that the three lighting circuits are all connected to it at the same point.
What is the voltage drop at the end of the lighting circuits?
Solution:

  • Voltage drop in the 4-wire line:  

Figure G28 shows 0.55 V/A/km
ΔU line = 0.55 x 150 x 0.05 = 4.125 V phase-to-phase
which gives: phase to neutral.

  • Voltage drop in any one of the lighting single-phase circuits:

ΔU for a single-phase circuit = 18 x 20 x 0.02 = 7.2 V
The total voltage drop is therefore
7.2 + 2.38 = 9.6 V

This value is satisfactory, being less than the maximum permitted voltage drop of 6%.



FigG30.jpg



























Fig. G30: Example 2
Personal tools